Pick the right rack UPS by checking load in watts, rack units, runtime, online vs line-interactive design, plugs and management cards. Simple checklist.
A rack-mounted UPS fits in a standard 19 inch rack and protects servers, switches and storage from outages and power problems. Use these steps to choose one.
Add up the maximum watts of every device that will plug into the UPS. Add 20 to 30 percent for growth. Use the UPS's watt rating, not only its VA rating. Example: 2,000 W of gear plus 25 percent growth means a UPS rated for at least 2,500 W.
Rack UPS units commonly come in 1U, 2U, 3U and larger sizes. Larger capacity usually means more height and more weight. Check the depth of your rack and the weight the rails can hold, and put heavy UPS units at the bottom.
Decide how long you need. Five to fifteen minutes is enough for a clean shutdown. If you need an hour or more, add extended battery modules or plan a generator. Use the manufacturer's runtime chart for your load.
Check the input plug and the outlet types (C13 and C19) against your servers and power cords. Higher capacity models often need a 20 A or 30 A circuit, which an electrician may have to install.
A network management card lets you watch the UPS remotely and shut servers down safely when the battery runs low.
Lithium-ion batteries last longer than sealed lead-acid but cost more up front. Look for hot-swappable batteries, a maintenance bypass, and a warranty that includes the battery.
For high-availability rooms, use two UPS units in an N+1 setup so one can fail without dropping the load.