Most racks need two PDUs for A/B redundancy. Learn how to calculate load, outlets and amperage so you buy the right number of rack PDUs.
One connects to power feed A and the other to feed B, so the rack stays on if one circuit fails. Small racks with only a few devices can run on one PDU.
List the maximum watts for each device. Add them, then add 20 percent for growth. Example: 4,000 W of equipment plus growth equals about 4,800 W.
Electrical codes in the US limit continuous load to 80 percent of a circuit's rating. A 208 V, 30 A single-phase circuit supplies about 6,240 VA, so plan for roughly 4,990 VA of continuous load per PDU. With A/B redundancy, each PDU should be able to carry the whole rack alone if the other fails, so split the load with that in mind.
Count the plugs you need. Servers usually use C13 outlets. Larger devices may need C19. Add spare outlets for future gear.
Rule of thumb: buy two PDUs sized so either one can carry the full load.