The Eaton EMPDT1H1C2 is an environmental monitoring probe designed to capture temperature, humidity, and discrete contact status in IT racks and power infrastructure. It is deployed by data center engineers, facilities teams, and network technicians to augment UPS or managed PDU systems with environmental sensing where ambient conditions must be tracked to prevent heat- or humidity-related failures. This accessory solves the absence of integrated environmental sensors on many power devices by providing field-installable probe capability.
This Gen 2 probe supports temperature and relative humidity measurement, plus two dry contact inputs for additional alarms (e.g., door switches or leak detectors). When connected to a compatible host (e.g., Eaton Network-M2, Network-M3 management card, or supported managed rack PDU), these metrics are made available over the host's network management interface for remote visibility and alerting.
Mechanically, the probe is a compact module with wired connectivity and multiple mounting options, including tie-wrap, magnet, or bracket placement within enclosures or adjacent to critical equipment. Typical deployment points are rack intakes or exhausts, cabinet mid-elevation, or near potential moisture-entry zones.
Integration requires a compatible Eaton network interface card or managed PDU with sensor port support; it does not function independently or with generic network appliances. When properly connected, the system can provide threshold alerts, SNMP traps, or environmental dashboards to management platforms.
A practical deployment is adding EMPDT1H1C2 probes at the top, middle, and bottom of a high-density rack to monitor thermal gradients and humidity variations, aiding in airflow optimization and preventive maintenance. This unit is not appropriate as a standalone data logger or for direct connection to building automation without a supported Eaton host interface.
| Specification | Detail |
|---|---|
| Brand | Eaton |
| Part Number | EMPDT1H1C2 |
| Product Type | Environmental Monitoring Probe |
| Sensor Type | Temperature & humidity + 2 dry contacts |
| Temperature Range | 0 °C to 70 °C |
| Humidity Range | 10 % to 90 % RH |
| Accuracy (Temp) | ± 2 °C typical |
| Accuracy (Humidity) | ± 5 % typical |
| Connectivity | Wired probe to host network card |
| Applicable Hosts | Eaton Network-M2 / Network-M3 & supported PDUs |
| Mounting | Magnet, tie-wrap, bracket |
| LED Indicator | Status/health LED on unit |
| Weight | ~34 g |
| Dimensions | ~57.6 × 37.6 × 29.3 mm |
| Compliance | CE marked |
| Operating Humidity | 10 %-90 % non-condensing |
| Operating Temp | 0 °C-70 °C |
All packages are shipped same day if the order is placed before 3PM CST
We use UPS/FedEx to ship the packages with different service levels offered by UPS/FedEx
Overnight Shipping take 1 business day
Expedited Shipping take about 2-3 business days
Ground shipping take about 3-5 business days
You can select the desired service level at Checkout and we will make sure the package is shipped as per the selected service level.
We Accept
i) PayPal
ii) All Credit & Debit Cards
iii) Purchase Orders
iv) Check
v) Bank Transfer/ACH/Wire Transfer
To process the order through Paypal/CC, you can simply checkout and process the payment.
If you want to issue us Purchase Order/Check/Bank Transfer, Please contact us at the following details
Call: 469.458.9636
Email: sales@dcsupplies.net
If you have any queries, please contact us at the following details and we will be happy to help
Call
469.458.9636
469.458.9638
Email
sales@dcsupplies.net