Calculate PDU load in 3 steps. Get the watts, amps and volts formula, the 80% rule and a worked 208V example to avoid tripped breakers.
PDU load is the total power your devices draw, compared with the power the PDU and its circuit can safely supply.
Watts = volts x amps. To find amps from watts, use amps = watts / volts. For three-phase power, multiply by 1.732: watts = volts x amps x 1.732.
Electrical codes in many regions treat a continuous load as safe only up to 80% of the circuit rating. This derating protects the circuit breaker and wiring from overload. Local rules vary, so confirm with a licensed electrician.
| Circuit | Maximum | Safe continuous load (80%) |
|---|---|---|
| 120V, 20A single-phase | 2,400 W | 1,920 W |
| 208V, 30A single-phase | 6,240 W | 4,992 W |
| 208V, 30A three-phase | 10,808 W | 8,646 W |
A rack holds 10 servers that draw 350 W each. That is 3,500 W, or about 16.8 amps at 208V. On a 208V, 30A circuit, the safe limit is 4,992 W, so the load is about 70% of the safe limit. That works, with room to add one or two devices.
With A and B feeds, keep each below 40% so one feed can carry the whole rack if the other fails. Also check each outlet bank, and stagger server start-up so inrush current does not trip a breaker.